Crew setting Verti-Block units with an excavator and block grab on a gravel leveling pad

Reference

Verti-Block design data

The numbers engineers and estimators ask for most: block dimensions and weights, gravity wall heights, mass extenders, geogrid, drainage and installation.

  • 7 min read
  • 10 sections
  • Updated

The short answer

Verti-Block is a hollow-core precast retaining wall system. The standard unit is 2 ft high, 4 ft wide and 3 ft deep and weighs about 1,760 lb. Published design tables show gravity walls from 5.5 ft to 19 ft without geogrid, depending on soil, surcharge and slope, and geogrid-reinforced walls to 30 ft and beyond.

Planning data, not a wall design. Every retaining wall needs a site-specific design by a licensed engineer. We draft free preliminary designs, and a licensed PE reviews and stamps the final design on approval.

Verti-Block standard unit: stone-textured face, hollow core and two cast-in lift loops
This is Verti-Block. One standard unit: 2 ft high, 4 ft wide, 3 ft deep, about 1,760 lb.

Meet the block

One big block, set by machine

Verti-Block is a hollow-core precast concrete block with a stone-textured face. An excavator sets each unit, raised lugs lock it to the course below, and crushed stone in the core adds weight and drains the wall from top to bottom.

Diagram of a Verti-Block unit: cast-in lift loops for machine setting, a hollow core filled with crushed stone, the stone core draining the full wall height, and raised lugs that lock into the notch under the block above
  • 2 × 4 × 3 ftStandard unit: 8 sq ft of wall face
  • ~1,760 lbEmpty; about 3,035 lb with stone in the cores
  • 5.5–19 ftPublished gravity heights, no geogrid
  • 304 sq ftWall face per truckload
Verti-Block wall with an outside corner and a curve around a lawn
Corners and curves
Verti-Block wall with stairs beside a modern home
Stairs and height steps
Stepped Verti-Block wall along a fence line
A top of wall that follows the grade
Tiered, curving Verti-Block wall on a hillside
Tiered walls

Standard unit: dimensions and weight

The standard block makes up about 90% of a typical Verti-Block wall. Each unit has hollow cores, a male/female connection that sets the batter automatically on every course, and a Canyon Ledge stone face.

PropertyValue
Size2 ft high × 4 ft wide × 3 ft deep (8 sq ft of face)
Weight, emptyAbout 1,760 lb
Weight, cores filled with gravelAbout 3,035 lb
FaceCanyon Ledge texture, 5 in. of relief
Standard batter2-3/16 in. per 24 in. course (about 5°)
Setback option12 in. per course (about 26°)
Zero-batter optionShear-lug blockouts (detail WD-31)
Minimum curve radius16 ft
TolerancesHeight ±1/8 in.; width and depth ±1/2 in.
Freeze-thawASTM C666, or an approved DOT mix

In plain terms Each standard block covers 8 sq ft of wall face. A wall 4 ft high and 40 ft long is 2 courses of 10 blocks: about 20 blocks.

The Verti-Block family

Every wall is built from a handful of shapes. The standard block does most of the work; the others handle ends, corners, the top course, height changes and the base.

  • Verti-Block standard unitStandardAbout 90% of a wall · 1,760 lb
  • Verti-Block top unit with a soil cutoutTopLets soil and grass run over the wall · 1,312 lb
  • Verti-Block half unitHalfWall ends, every other course · 1,070 lb
  • Verti-Block corner unit with a finished returnCorner90° outside corners · 1,600 lb
  • Verti-Block half-step unitHalf-step1 ft height changes · 970 lb
  • Verti-Block mass extender unitMass extenderBase courses of tall walls · 2,674 to 5,098 lb
UnitSizeApprox. weightUsed for
Standard4 × 2 ft face, 3 ft deep1,760 lbAbout 90% of a wall
Top4 × 2 ft face, soil cutout at the back1,312 lbTop course; soil and grass run over the wall
Half2 × 2 ft face, 3 ft deep1,070 lbWall ends, every other course
Corner4 × 2 ft face plus a finished 2 × 2 ft return1,600 lb90° outside corners (45° options available)
Half-step4 × 1 ft face970 lb1 ft height changes and exact heights
Mass extender48 to 84 in. deep2,674 to 5,098 lbBase courses of taller gravity walls

Design basis and material properties

  • Concrete: 142 pcf design unit weight; about 4,000 psi at 28 days.
  • Core fill: gravel at 110 pcf. Combined block and fill: about 126 to 131 pcf (composite design weight 126 pcf, 24.0 cu ft, center of gravity 18.14 in.).
  • Retained soil assumed in the tables: 120 pcf.
  • Factors of safety in the published tables: sliding 1.5, bearing 2.0. Overturning and other criteria are set in the site-specific design.
  • Minimum embedment: H/10, and never less than 6 in.
  • Leveling pad concrete, if used: 3,000 psi minimum.
  • Methodology: NCMA (3rd Edition) and AASHTO LRFD.

How tall can a Verti-Block gravity wall be?

Without any geogrid, published gravity heights run from 5.5 ft to 19 ft at the standard 5° batter with mass-extender base courses. The range depends on how strong the retained soil is, whether there is a surcharge (like a parking lot or a building) above the wall, and whether the ground slopes up behind it.

Published gravity wall heights, no geogrid (standard ~5° batter, mass-extender base courses)
Retained soil (friction angle)Level, no surchargeLevel, 250 psf surcharge2:1 sloping backfill
Silty (≥ 28°)7.5 to 13 ft5.5 to 11 ft5.5 to 7.5 ft
Sandy (≥ 30°)7.5 to 15 ft5.5 to 11 ft5.5 to 9.5 ft
Gravelly sand (≥ 35°)9.5 to 17 ft7.5 to 15 ft9.5 to 15 ft
Gravelly (≥ 40°)11 to 19 ft9.5 to 17 ft11 to 17 ft

In plain terms In good gravelly soil, the published tables show a Verti-Block wall holding back up to 19 ft of ground with no geogrid at all: just the weight of the blocks and the stone in their cores.

The published gravity tables do not include seismic loading. The free Verti-Block analysis software runs seismic and global-stability checks for a site-specific design.

Standard batter vs. the 12-inch setback

Laying each course back 12 in. (about a 26° batter) instead of the standard 2-3/16 in. (about 5°) lets a gravity wall go taller. In gravelly soil with mass extenders, the published height goes from 19 ft at the standard batter to 24.5 ft with the setback: about 5.5 ft more wall, gained through geometry instead of reinforcement. The trade-off is 12 in. of horizontal travel per course, so the wall needs more room at the top.

Side-by-side wall sections: a 19 ft wall at the standard batter of about 5 degrees, and a 24.5 ft wall with a 12-inch setback per course, about 26 degrees
Same blocks, different lean. Published gravity heights in gravelly soil with mass extenders: 19 ft at the standard batter, 24.5 ft with the 12-inch setback.

Mass extenders

Mass extenders are deeper units for the base courses. They put weight where the overturning force on a wall is greatest, so the wall can go taller as a gravity wall, inside the same narrow footprint, without a reinforced soil zone behind it. They typically backfill with compacted native soil, so no imported structural fill is needed.

Wall section with standard 3 ft deep units above and deeper mass extenders in the two base courses
Weight where it counts. Mass extenders go in the base courses only; standard units continue above.
UnitDepthApprox. weight
48 in. mass extender4 ft2,674 lb
60 in. mass extender5 ft3,509 lb
60 in. dual-cavity5 ft2,783 lb
72 in. mass extender6 ft4,297 lb
84 in. mass extender7 ft5,098 lb

They matter most when property lines, utilities or existing structures behind the wall rule out excavating for geogrid. The heaviest unit is about 5,100 lb, so walls are still set with an excavator.

Geogrid-reinforced walls

When a wall needs to go taller than gravity allows, geogrid (Stratagrid 200, 500 or 600) goes in every course at 2 ft spacing in the published designs. Grid length stays the same from top to bottom, which keeps take-offs simple.

Geogrid wall section with grid at 2 ft spacing reaching about 0.7 times the wall height on level ground, plus friction connection M-03 and positive connection WD-36 details
Grid in every course. About 0.7H on level ground, up to about 0.95H under a 2:1 slope. Friction connection (M-03) or grid looped through the hollow core (WD-36).
Published geogrid-reinforced heights (level backfill)
Retained soil (friction angle)No geogrid up toMax published heightGrid length at max height
Silty (≥ 28°)10 ft30 ft20.0 ft (Strata 600)
Sandy (≥ 30°)10 ft30 ft20.0 ft (Strata 600)
Gravelly sand (≥ 35°)12 ft30 ft+18.0 ft (Strata 600)
Gravelly (≥ 40°)14 ft30 ft+ (34 ft published)20.4 ft (Strata 500)
  • Grid length: about 0.65 to 0.70 times the wall height on level ground, up to about 0.95 times the height under a 2:1 slope. Minimum reinforcement length is 0.7H from the face.
  • Coverage: 100% horizontal coverage, at a maximum vertical spacing of 4 ft (two courses).
  • Connections: friction connection with the grid laid over the block (detail M-03), or a positive connection with the grid looped through the hollow core (detail WD-36).

Drainage

The design tables assume the backfill is drained, so drainage is part of the structure, not an accessory. Four details keep that assumption true:

Wall section numbered with the four drainage details: internal stone drainage column, base collection pipe, geotextile filtration, and surface grading away from the wall
  1. Drainage column: clean crushed stone of about 1 in. in the cores (ASTM D448, no more than 5% passing the No. 200 sieve) forms a continuous drain the full height of the wall.
  2. Base collection: perforated PVC or HDPE pipe, 3 in. minimum, in the bottom block cavity, or paired with 12 in. of gravel behind the wall where flows demand it (detail WD-16).
  3. Filter fabric: needle-punched non-woven geotextile, 120 lb minimum grab tensile (ASTM D4632), lapped 6 in., keeps fines out of the drainage stone.
  4. Surface water: finish grade sloped at least 2% away from the wall face.

Installation specification points

Excavator with a block grab setting a Verti-Block unit beside staged hollow-core units
An excavator and block grab set each unit.
Verti-Block unit lowered onto a compacted gravel leveling pad while a worker checks placement
Units go down on a compacted, level gravel pad.
  • Leveling pad: 6 in. minimum depth (12 in. where required), of crushed stone 1 ft wider than the block depth, or 3,000 psi concrete. It must be compacted, level and accepted before the first course goes down.
  • Foundation: proof-rolled, with bearing soils confirmed by the geotechnical engineer and unsuitable soils replaced.
  • First course: set over the drain pipe and leveled side to side and front to back. It is the critical course.
  • Stacking: running bond, with each female notch set over the male riser and pulled forward to set the batter.
  • Backfill soils: liquid limit under 45 and plasticity index under 20; fat clays and oversized rock excluded unless the geotechnical engineer approves.
  • Compaction: lifts of 12 in. maximum to the density in the project specification, with only hand-operated compactors within 3 ft of the wall. Test at least every 2 vertical ft and every 50 lineal ft.

Design tools and support

  • Free analysis and design software: gravity and reinforced design to NCMA, AASHTO ASD/LRFD and CAN-CSA, with seismic and global-stability checks, plan-to-layout conversion, block counts, geogrid schedules and CAD export. Available at verti-block.com.
  • Design manual and details: the Verti-Crete Design Manual, block detail sheets (BD-01 to BD-15), wall details and SketchUp models, at verti-block.com.
  • Free preliminary design from Natrix: send a grading plan and the wall line, and we return a preliminary design with block counts, the mass-extender layout, geogrid requirements and a budget number. A licensed PE reviews and stamps the final design on your approval.

For how these numbers play out on real projects, see the highway and roadway guide and the commercial grade-change guide, or the Verti-Block overview.

Source: Verti-Crete Design Manual, Release 4.1, and Verti-Block product data sheets. Weights are approximate.

FAQ

Common questions

How tall can a Verti-Block gravity wall be without geogrid?

The published design tables show gravity walls from 5.5 ft to 19 ft at the standard 5° batter, depending on soil strength, surcharge and backslope, with mass-extender base courses. Gravelly soils reach the top of that range. With the 12-inch setback option, published heights reach 24.5 ft in gravelly soil. Every wall needs a site-specific design.

How much does a Verti-Block block weigh?

A standard unit (2 ft high, 4 ft wide, 3 ft deep) weighs about 1,760 lb empty and about 3,035 lb once its cores are filled with gravel. Mass extenders for the base course weigh from 2,674 lb (48 in. deep) to 5,098 lb (84 in. deep).

What design standards are Verti-Block walls designed to?

The published tables use NCMA (3rd Edition) and AASHTO LRFD methodology. The free Verti-Block analysis software designs gravity and reinforced walls to NCMA, AASHTO ASD/LRFD and CAN-CSA, with seismic and global-stability checks.

What is the minimum curve radius for a Verti-Block wall?

16 ft. The system handles convex and concave curves, and corner blocks form 90° and 45° corners.

What goes in the hollow cores?

Clean crushed stone of about 1 inch (ASTM D448 gradation, no more than 5% passing the No. 200 sieve). It adds weight to the wall and forms a continuous drain the full height of the wall.

Get a free preliminary wall design.